VFD Shutdown on Minimum Speed: Account for Drift and Add Timeout

The Scenario

A Variable Frequency Drive (VFD) is programmed to shut down when the motor reaches minimum speed. However, the PLC logic checks for an exact speed threshold — and the actual feedback from the VFD drifts slightly around that value. The result: the shutdown condition is either never met (motor runs forever at min speed) or triggers intermittently.

The Root Cause

Current feedback and speed feedback from VFDs are analog signals — they fluctuate due to:

  • A/D converter noise in the VFD or PLC input card.
  • Motor load variations causing actual speed to oscillate around the setpoint.
  • Communication latency if feedback is read via Modbus/Ethernet rather than hardwired analog.

The Fix

1. Add Margin for Error

Do not check for speed == min_speed. Instead, use a range:

IF speed_feedback <= (min_speed + margin) THEN start_shutdown_timer

A margin of 2-5% of the speed range is typical. This accounts for feedback drift without triggering prematurely.

2. Add a Timeout

Use a timer that starts when the speed command is at minimum and the VFD is still running. If the condition persists for a defined period (e.g., 10-30 seconds), execute the shutdown. This prevents the VFD from sitting at minimum speed indefinitely if the feedback-based shutdown condition is not met cleanly.

3. Combined Approach

IF (speed_cmd == min_speed) AND (speed_feedback <= min_speed + margin) AND (timer.DN) THEN stop_VFD

Additional Consideration

Monitor the VFD current feedback at min speed. If current is near zero or behaving erratically, the feedback signal may be unreliable at low speeds — use the timeout as the primary shutdown mechanism rather than relying on speed feedback alone.


Contact

Email: info@eliteautomation.ca

Phone: (587) 735-3548

150-17510 107 Ave NW, Edmonton, AB, T5S 1E9, Canada